P/N AD111101NA 10/13 Rev. C
WARNING
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas suppliers
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clear-
ances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
Addison
7050 Overland Road
Orlando, Florida 32810
Telephone: +1.407.292.4400
Fax: +1.407.290.1329
www.addison-hvac.com
© 2013 Addison
Installation, Operation
& Service Manual
Models UHA[T][X][S]
150, 175, 200, 225
250, 300, 350, 400
UHA-Series
Tubular Unit Heaters
(Standard Range)
Page view 0
1 2 3 4 5 6 ... 73 74

Summary of Contents

Page 1 - (Standard Range)

P/N AD111101NA 10/13 Rev. CWARNINGFOR YOUR SAFETYIf you smell gas: 1. Open windows. 2. DO NOT try to light any appliance. 3. DO NOT use electri

Page 2

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL2 of 59Figure 1: UHA[T][X][S]150 - 250 Label Placement*For separated combustion unit

Page 3 - (Gamme standard)

SECTION 1: HEATER SAFETY 3 of 59Figure 2: UHA[X][S]300 - 400 Label Placement*For separated combustion units only.Description Part NumberLogo Label 910

Page 4

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL4 of 59SECTION 2: INSTALLER RESPONSIBILITYThe installer is responsible for the follo

Page 5 - Printed in U.S.A

SECTION 3: CRITICAL CONSIDERATIONS 5 of 59SECTION 3: CRITICAL CONSIDERATIONS3.1 Basic InformationUHA[T][X][S] heaters have automatic ignition burners

Page 6

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL6 of 59SECTION 4: CLEARANCES TO COMBUSTIBLES4.1 Required Clearances to CombustiblesW

Page 7 - TABLE OF FIGURES

SECTION 4: CLEARANCES TO COMBUSTIBLES 7 of 59Figure 3: Installation Clearances and Clearances to Combustibles6"(15 cm)31"**(79 cm)3"(8

Page 8

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL8 of 59SECTION 5: NATIONAL STANDARDS AND APPLICABLE CODES5.1 Gas CodesThe type of ga

Page 9

5.6 High AltitudeThese heaters are approved (without modifications) for installations up to 2000' (610 m) in US and Canada. Heaters installed abo

Page 10

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL10 of 59SECTION 6: HEATER INSTALLATION 6.1 General Heaters are designed for installa

Page 11 - SECTION 1: HEATER SAFETY

SECTION 7: VENTING 11 of 59SECTION 7: VENTINGWARNINGCarbon Monoxide HazardHeaters may be installed vented or unvented.Vented heaters must be vented ou

Page 13 - RITICAL CONSIDERATIONS

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL12 of 597.2.1 Standard Vented Heaters (Models UHA[T][X] 150-250 and Models UHA[X] 3

Page 14

SECTION 7: VENTING 13 of 597.8 Replacing an Existing Heater in a Venting SystemWhen replacing an existing heater in a venting system, the venting syst

Page 15 - Installation Clearances

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL14 of 59Figure 6: Standard Vented Heater - Vertical and Horizontal Vent TerminationV

Page 16

SECTION 7: VENTING 15 of 59Figure 7: Standard Vented Heater - Common Vertical Vent TerminationRoof2'(.6 m)MinimumType "B" vent cap (7&

Page 17

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL16 of 59Figure 8: Separated Combustion Heater - Vertical and Horizontal Vent Termina

Page 18

SECTION 7: VENTING 17 of 59Figure 10: Concentric Vertical and Horizontal Vent TerminationVent**Air Intake*ConcentricVent BoxVerticalOption10' (3

Page 19 - SECTION 7: VENTING

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL18 of 59SECTION 8: AIR SUPPLYWARNINGExplosion HazardEquipment must have access to un

Page 20

SECTION 9: GAS PIPING 19 of 59SECTION 9: GAS PIPINGWARNINGFire HazardConnect gas supply according to Figure 11.Do not use gas supply pipe and electric

Page 21

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL20 of 59Figure 11: Gas ConnectionGas Shut-off ValveDrip LegCapUnionConnectionOption

Page 22 - 14 of 59

SECTION 10: WIRING 21 of 59SECTION 10: WIRINGDANGERElectrical Shock HazardDisconnect electric before service.More than one disconnect switch may be re

Page 23

Addison7050 Overland RoadOrlando, Florida 32810Téléphone: +1.407.292.4400Fax: +1.407.290.1329www.addison-hvac.com© 2013 AddisonManuel d’installation,

Page 24 - Figure 9: Concentric Vent Box

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL22 of 5910.2 Low Voltage Thermostat with One Heater for Models UHA[T][X][S] 150-250T

Page 25 - 17 of 59

SECTION 10: WIRING 23 of 5910.4 Low Voltage Thermostat with Multiple Heaters (Models UHA[T][X][S]150 - 250)NLGnd.NLGnd.LNGnd.120V-60 HzNOTE: If both t

Page 26

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL24 of 5910.5 Low Voltage Thermostat with Multiple Heaters (Models UHA[X][S]300 - 400

Page 27 - SECTION 9: GAS PIPING

SECTION 10: WIRING 25 of 5910.6 UHA[X][S] Series Internal Wiring Diagram for Single Stage Gas ValvesNOTE:For field wiring into service junction box, o

Page 28

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL26 of 5910.7 UHA[X][S] Series Ladder Wiring Diagram for Single Stage Gas ValvesNOTE:

Page 29 - SECTION 10: WIRING

SECTION 10: WIRING 27 of 5910.8 UHA[T][X][S] Series Internal Wiring Diagram for Two Stage Gas Valves1W2HIGH/LOW CONTROLHIGHLOWCOMMONNOTE:For field wir

Page 30 - NOTE: Electrical supply is

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL28 of 5910.9 UHA[T][X][S] Series Ladder Wiring Diagram for Two Stage Gas ValvesHIGHS

Page 31 - 23 of 59

SECTION 10: WIRING 29 of 5910.10 Electrical Connection to the HeaterNote: Junction box is not provided with heater. Conduit can also be attached dire

Page 32 - 24 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL30 of 59SECTION 11: OPERATION AND MAINTENANCECut/Pinch HazardWear protective gear du

Page 33

SECTION 11: OPERATION AND MAINTENANCE 31 of 5911.2 Begin Start-Up 11.2.1 Before Operating the HeaterTo ensure that all the controls are in safe wor

Page 35

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL32 of 59Figure 13: Single Stage Gas Valve for Models UHA[X][S] 150-400½PSI INCONOFFR

Page 36

SECTION 11: OPERATION AND MAINTENANCE 33 of 5911.2.2 Start-Up the Gas Valve (All Gases)11.2.2.1 Check Burner Gas Pressure1. Remove the plug in the out

Page 37 - 29 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL34 of 59SECTION 12: USER INSTRUCTIONSCut/Pinch HazardWear protective gear during ins

Page 38

SECTION 13: SERVICING 35 of 59SECTION 13: SERVICINGCut/Pinch HazardWear protective gear during installation, operation and service.Edges are sharp.WAR

Page 39 - PERATION AND MAINTENANCE

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL36 of 59Page 47, Section 15.3.1. Clean any deposits from the main burner which may h

Page 40 - 32 of 59

SECTION 13: SERVICING 37 of 59Vent Pipe/Terminals Venting must be intact. Using a flashlight, look for obstructions, cracks on the pipe, gaps in the s

Page 41

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL38 of 59Silicone Tubing Ensure tight, secure fit on all pressure fittings at pressur

Page 42

SECTION 14: TROUBLESHOOTING 39 of 59SECTION 14: TROUBLESHOOTINGCut/Pinch HazardWear protective gear during installation, operation and service.Edges a

Page 43 - ERVICING

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL40 of 5914.1 General

Page 44

SECTION 14: TROUBLESHOOTING 41 of 5914.2 Troubleshooting For Automatic Ignition Burner Systems For your safety and optimum heater performance, use onl

Page 45 - SECTION 13: SERVICING

© 2013 AddisonAll rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - gra

Page 46

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL42 of 5914.3 Troubleshooting for Flame Supervision SystemNOTE: Minimum flame probe c

Page 47 - SECTION 14: TROUBLESHOOTING

SECTION 14: TROUBLESHOOTING 43 of 5914.4 Troubleshooting for Gas Valves14.5 Troubleshooting for Flue BlowerFor your safety and optimum heater performa

Page 48 - 14.1 General

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL44 of 59SECTION 15: REPLACEMENT PARTSCarbon Monoxide HazardWARNINGUse only genuine A

Page 49

SECTION 15: REPLACEMENT PARTS 45 of 5915.2 Burner Compartment for Models UHA[T][X][S] 150-250FillerPanelBurnerAssemblySide View of Burner Compartment

Page 50 - 42 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL46 of 5915.2.2 Remove 4 screws to remove manifold.Ensure gas tight fitting of inject

Page 51

SECTION 15: REPLACEMENT PARTS 47 of 5915.3 Burner Compartment for Models UHA[X][S] 300-400Remove flexibleair duct from spigot Removeaccess plateRemove

Page 52 - Two Stage

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL48 of 5915.4 Ignition Electrode and Flame Probe for Models UHA[T][X][S] 150-250Descr

Page 53 - Assembly

SECTION 15: REPLACEMENT PARTS 49 of 5915.5 Ignition Electrode and Flame Probe for Models UHA[X][S] 300-400InshotBurnersInshotBurnersBurner Compartment

Page 54

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL50 of 5915.6 Heat Exchanger The heat exchanger consists of a four-pass design with 1

Page 55 - Propane (G31)

SECTION 15: REPLACEMENT PARTS 51 of 5915.8 Flue Blower for Models UHA[T][X][S] 150-175Rear PanelGasketMountingPlateFlue FanVent BoxRear PanelFlue FanV

Page 56

15.12 Ignition Control... 5415.13 Axial Fan/Guard/Motor Assembly... 5415.1

Page 57 - 49 of 59

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL52 of 5915.9 Flue Blower for Models UHA[T][X][S] 200-300 Outlet Gasket(Inside of Rea

Page 58 - Horizontal

SECTION 15: REPLACEMENT PARTS 53 of 5915.10 Flue Blower for Models UHA[X][S] 350-400 Vent BoxOutletGasketFlue BlowerVent BoxscrewsFlueAdapterFlue Adap

Page 59 - 150 - 175

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL54 of 5915.11 Pressure SwitchCarbon Monoxide HazardUse correct pressure switch speci

Page 60 - Fan Plate Screws

SECTION 15: REPLACEMENT PARTS 55 of 5915.13.1 Fan Removal and ReplacementWARNINGSevere Injury HazardTurn off gas and electrical supply before service.

Page 61 - 350 - 400

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL56 of 59SECTION 16: SPECIFICATIONS16.1 Dimension Data for Models UHA[T][X][S] 150-25

Page 62

SECTION 16: SPECIFICATIONS 57 of 5916.2 General Technical Data TableModelUHA[T][X][S]150UHA[T][X][S]175UHA[T][X][S]200UHA[T][X][S]225UHA[T][X][S]250Fu

Page 63 - Description Part Number Qty

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL58 of 5916.4 Dimension Data for Models UHA[X][S] 300-400ABFGHHeater must be supporte

Page 64 - SECTION 16: SPECIFICATIONS

Model UHA[X][S]300 UHA[X][S]350 UHA[X][S]400A in (cm) 52.3 (132.8) 52.3 (132.8) 52.3 (132.8)B in (cm) 43.2 (109.7) 43.2 (109.7) 43.2 (109.7)C in (cm)

Page 65 - 16.3 Technical Data Table

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL60 of 59

Page 66 - 58 of 59

SECTION 17: THE ADDISON® UHA-SERIES WARRANTY 61 of 59SECTION 17: THE ADDISON® UHA-SERIES WARRANTYADDISON WILL PAY FOR:Within 24 months from date of pu

Page 67 - 16.6 Technical Data Table

TABLE OF FIGURESFigure 1: UHA[T][X][S]150 - 250 Label Placement ...2Figure 2: UHA[X][S]300 - 400 Label Placement...

Page 74

SECTION 1: HEATER SAFETY 1 of 59SECTION 1: HEATER SAFETYYour Safety is Important to Us! This symbol is used throughout the manual to notify you of po